Rancang Bangun Sistem Monitoring Electrical Conductivity Berbasis PLC S7-1200 dan Node Red Pada Area BOP 2 PT. Krakatau Chandra Energy
DOI:
https://doi.org/10.53026/kptsn004Keywords:
PLC S7-1200, Monitoring, Electrical Conductivity, Demineralized Water, Node-REDAbstract
This study aims to design and implement an Electrical Conductivity (EC) monitoring system in the Balance of Plant (BOP) 2 area, specifically in the demineralized water unit, to facilitate remote monitoring without requiring on-site inspection. The system integrates the EC Analyzer Rosemount 1066, power supply, HMI KTP600, Siemens S7-1200 PLC, and Real-time data visualization using Node-RED with remote access via Portmap.io. The methodology includes literature review, system design, prototype development, and field testing. Test results show that the system operates responsively, with EC reading deviations of approximately ±0.1% and an average delay of 1.93 seconds. The system proves to be accurate, responsive, and suitable for industrial application, with suggestions for future development including SOP creation and system expansion to other plant parameters. This system enables more efficient and safer monitoring by reducing the need for field inspections. Its implementation supports digital transformation in industrial utility management
References
[1] Atlas Scientific, “No Title,” 2022. https://atlas-scientific.com/blog/how-does-conductivity-affectwater-quality/
[2] Agung, “Sistem Monitoring Kualitas Air dari Zat Berbahaya,” October 13, 2022, 2022. https://testindo.co.id/sistem-monitoring-kualitas-air-dari-zat-berbahaya/
[3] Muslimin and S. N. Jabir, “Implementation of Forward Reverse Control and Monitoring on Three Phase Motor with Siemens S7-1200 PLC Based on LabView HMI and OPC,” JEAT J. Electr. Autom. Technol., vol. 2, no. 1, pp. 39–45, 2023, doi: 10.61844/jeat.v2i1.513.
[4] S. C. ABADI, N. W. NUGRAHA, I. A. DHIMYATI, and A. H. SUMARSO, “Penerapan Human Machine Interface Berbasis Augmented Reality pada Sistem SCADA Modular Production System,” ELKOMIKA J. Tek. Energi Elektr. Tek. Telekomun. Tek. Elektron., vol. 11, no. 2, p. 285, 2023, doi: 10.26760/elkomika.v11i2.285.
[5] A. D. IRFAN, “Penerapan Aplikasi Node-Red pada Sistem SCADA Plan Testing Station Dan Handling Station,” 2022. https://eperpustakaan.polmanbandung.ac.id/index.php?p=show_detail&id=18595
[6] S. M. Sumit Shinde, “Integrating Siemens S7 PLCs with Node-RED,” 17 Jan, 2025, 2025. https://flowfuse.com/blog/2025/01/integrating-siemens-s7-plcs-with-node-red-guide/
[7] M. R. Saputra, “No Title,” May 8 , 2024, 2024. https://www.mertani.co.id/post/mengoptimalkanpemantauan-kualitas-air-secara-akurat-dan-real-time-menggunakan-water-quality-monitor
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Ledyna Meichelia, Suka Handaja

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.